ENERGY PERFORMANCE ASSESSMENT OF HOTEL BUILDINGS IN VARADERO, CUBA
Keywords:
energy baseline, energy management, energy performance, hotel industryAbstract
Introduction:
Hotels are among the most energy-intensive building types; improving their efficiency offers both economic and environmental benefits. Reliable assessment of energy performance requires statistically validated baselines and performance indicators.
Objective:
To evaluate the energy performance of hotel buildings in Varadero, Cuba, using statistically derived baselines and performance metrics.
Materials and Methods:
Baseline energy consumption (EnB) was established for 15 hotels using the IDELIN_Hotel software tool, which integrates occupancy and cooling degree days (CDD) into a combined variable (Room Degree Days, RDD). Statistical validity was verified using the correlation coefficient (R2), the mean squared error coefficient of variation (CV-RMSE), and the normalized mean error coefficient (NMBE). Performance in the subsequent year was evaluated using specific energy consumption (Cee), non-service energy (Eo), energy variance (Ev), and cumulative sum of deviations (CUSUM).
Results and Discussion:
Twelve hotels achieved energy savings relative to their baselines, while three operated inefficiently. The best performance was observed in Hotel K, which saved 1300 MWh/year. Indicators highlighted the influence of occupancy and outdoor temperature on consumption patterns.
Conclusions:
The study confirms the statistical robustness of the baselines and demonstrates the utility of IDELIN_Hotel software tool for energy performance assessment. Comparative analysis of indicators provides actionable insights for energy management systems in the hotel sector.
Downloads
Downloads
Published
How to Cite
Issue
Section
License

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.